The seasonal energy performance of a cooling system based on an innovative variablegeometry ejector (VGE) is numerically investigated by using TRNSYS. The VGE-based system is mainly driven by solar energy, collected through solar thermal collectors, and is coupled to a residential building located in Porto. A biomass boiler is used as back-up heater. The energy performance of the investigated cooling system is compared with that of a conventional solution, based on a commercial air-to-water chiller. Results point out that, almost 75% of the generator heat demand can be supplied by solar collectors and about 90% of the overall energy input of the ejector-based system is satisfied by renewables. Moreover, numerical simulations confirm how the capability to vary the ejector geometry on the basis of current operating conditions allows to strongly improve the ejector seasonal efficiency. A second series of simulations aimed to further enhance the system performance. A master control logic which extends the VGE operation time in correspondence of favourable ambient conditions was introduced, in order to store additional cooling energy in the cold buffer tank. This strategy has proved to be effective, since the energy consumption of the biomass boiler could be reduced up to 35%.

Dongellini, M., Naldi, C., Moser, C., Varga, S., Morini, G.L. (2021). Primary energy saving potential of a solar-driven ejector cooling system: a case study for a Portuguese residential building. Bristol : IOP Publishing [10.1088/1742-6596/2116/1/012117].

Primary energy saving potential of a solar-driven ejector cooling system: a case study for a Portuguese residential building

Dongellini, M
Primo
;
Naldi, C;Morini, G L
2021

Abstract

The seasonal energy performance of a cooling system based on an innovative variablegeometry ejector (VGE) is numerically investigated by using TRNSYS. The VGE-based system is mainly driven by solar energy, collected through solar thermal collectors, and is coupled to a residential building located in Porto. A biomass boiler is used as back-up heater. The energy performance of the investigated cooling system is compared with that of a conventional solution, based on a commercial air-to-water chiller. Results point out that, almost 75% of the generator heat demand can be supplied by solar collectors and about 90% of the overall energy input of the ejector-based system is satisfied by renewables. Moreover, numerical simulations confirm how the capability to vary the ejector geometry on the basis of current operating conditions allows to strongly improve the ejector seasonal efficiency. A second series of simulations aimed to further enhance the system performance. A master control logic which extends the VGE operation time in correspondence of favourable ambient conditions was introduced, in order to store additional cooling energy in the cold buffer tank. This strategy has proved to be effective, since the energy consumption of the biomass boiler could be reduced up to 35%.
2021
EUROTHERM-2021 : 8th European Thermal-Sciences Conference : Proceedings
1
4
Dongellini, M., Naldi, C., Moser, C., Varga, S., Morini, G.L. (2021). Primary energy saving potential of a solar-driven ejector cooling system: a case study for a Portuguese residential building. Bristol : IOP Publishing [10.1088/1742-6596/2116/1/012117].
Dongellini, M; Naldi, C; Moser, C; Varga, S; Morini, G L
File in questo prodotto:
File Dimensione Formato  
Dongellini_Eurotherm 2021.pdf

accesso aperto

Tipo: Versione (PDF) editoriale
Licenza: Licenza per Accesso Aperto. Creative Commons Attribuzione (CCBY)
Dimensione 869.67 kB
Formato Adobe PDF
869.67 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/843183
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? ND
social impact