This position paper by the DEIS HVDC Cable Systems Technical Committee provides a review of existing diagnostic electrical and dielectric techniques for testing the insulation of polymeric extruded HVDC cable joints in the present Part 1. Here, the state of the art on the insulation of HVDC extruded cable system joints is covered with reference to types, design and testing techniques. This helps to identify routine tests as the first target for the onset of new testing procedures, AC-PD measurements as the readily-available measurement from manufacturers' practices for quality control of the insulation of accessories during routine tests and VHF/UHF wireless sensors as the best tool for performing such measurements on joints in the noisy factory environment. Thereby, a novel protocol for the measurement of partial discharges using AC voltages and VHF/UHF sensors, for quality control during routine tests on such joints, is derived in the next Part 2. This protocol is the main novelty of this investigation.

The insulation of HVDC extruded cable system joints. Part 1: Review of materials, design and testing procedures / Mazzanti G.; Castellon J.; Chen G.; Fothergill J.C.; Fu M.; Hozumi N.; Lee J.H.; Li J.; Marzinotto M.; Mauseth F.; Morshuis P.; Reed C.; Troia I.; Tzimas A.; Wu K.. - In: IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION. - ISSN 1070-9878. - STAMPA. - 26:3(2019), pp. 8726046.964-8726046.972. [10.1109/TDEI.2019.8726046]

The insulation of HVDC extruded cable system joints. Part 1: Review of materials, design and testing procedures

Mazzanti G.;
2019

Abstract

This position paper by the DEIS HVDC Cable Systems Technical Committee provides a review of existing diagnostic electrical and dielectric techniques for testing the insulation of polymeric extruded HVDC cable joints in the present Part 1. Here, the state of the art on the insulation of HVDC extruded cable system joints is covered with reference to types, design and testing techniques. This helps to identify routine tests as the first target for the onset of new testing procedures, AC-PD measurements as the readily-available measurement from manufacturers' practices for quality control of the insulation of accessories during routine tests and VHF/UHF wireless sensors as the best tool for performing such measurements on joints in the noisy factory environment. Thereby, a novel protocol for the measurement of partial discharges using AC voltages and VHF/UHF sensors, for quality control during routine tests on such joints, is derived in the next Part 2. This protocol is the main novelty of this investigation.
2019
The insulation of HVDC extruded cable system joints. Part 1: Review of materials, design and testing procedures / Mazzanti G.; Castellon J.; Chen G.; Fothergill J.C.; Fu M.; Hozumi N.; Lee J.H.; Li J.; Marzinotto M.; Mauseth F.; Morshuis P.; Reed C.; Troia I.; Tzimas A.; Wu K.. - In: IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION. - ISSN 1070-9878. - STAMPA. - 26:3(2019), pp. 8726046.964-8726046.972. [10.1109/TDEI.2019.8726046]
Mazzanti G.; Castellon J.; Chen G.; Fothergill J.C.; Fu M.; Hozumi N.; Lee J.H.; Li J.; Marzinotto M.; Mauseth F.; Morshuis P.; Reed C.; Troia I.; Tzimas A.; Wu K.
File in questo prodotto:
File Dimensione Formato  
final paper part 1.R1 OAcov.pdf

Open Access dal 30/05/2021

Tipo: Postprint
Licenza: Licenza per accesso libero gratuito
Dimensione 930.32 kB
Formato Adobe PDF
930.32 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/691738
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 57
  • ???jsp.display-item.citation.isi??? 36
social impact