Monitoring units for the measurement of highfrequency voltage transients have been in operation at three different busses of an Italian medium voltage (MV) distribution feeder, mainly composed by overhead lines, in March 2007 – August 2008. The feeder is located in a region characterized by a high ground flash density value (4 flashes/km2/yr); many of the recorded voltage transients may be correlated with the lightning events detected for the same region by the Lightning Location System (LLS) CESISIRF. The paper presents some experimental results obtained using the monitoring units and their comparison with computer results obtained using a LIOV-EMTP model of the considered MV feeder. A procedure aimed at achieving the best fit between measurements and calculations, which takes into account the uncertainties associated with LLS data, is also presented.

M. Bernardi, A. Borghetti, F. Napolitano, C.A. Nucci, M. Paolone, W. Schulz (2009). VOLTAGE TRANSIENTS IN A DISTRIBUTION NETWORK CORRELATED WITH EVENTS IDENTIFIED BY A LIGHTNING LOCATION SYSTEM. SAO PAULO : University of Sao Paulo.

VOLTAGE TRANSIENTS IN A DISTRIBUTION NETWORK CORRELATED WITH EVENTS IDENTIFIED BY A LIGHTNING LOCATION SYSTEM

BORGHETTI, ALBERTO;NAPOLITANO, FABIO;NUCCI, CARLO ALBERTO;PAOLONE, MARIO;
2009

Abstract

Monitoring units for the measurement of highfrequency voltage transients have been in operation at three different busses of an Italian medium voltage (MV) distribution feeder, mainly composed by overhead lines, in March 2007 – August 2008. The feeder is located in a region characterized by a high ground flash density value (4 flashes/km2/yr); many of the recorded voltage transients may be correlated with the lightning events detected for the same region by the Lightning Location System (LLS) CESISIRF. The paper presents some experimental results obtained using the monitoring units and their comparison with computer results obtained using a LIOV-EMTP model of the considered MV feeder. A procedure aimed at achieving the best fit between measurements and calculations, which takes into account the uncertainties associated with LLS data, is also presented.
2009
Proceedings of the X International Symposium on Lightning Protection (SIPDA)
533
538
M. Bernardi, A. Borghetti, F. Napolitano, C.A. Nucci, M. Paolone, W. Schulz (2009). VOLTAGE TRANSIENTS IN A DISTRIBUTION NETWORK CORRELATED WITH EVENTS IDENTIFIED BY A LIGHTNING LOCATION SYSTEM. SAO PAULO : University of Sao Paulo.
M. Bernardi; A. Borghetti; F. Napolitano; C.A. Nucci; M. Paolone; W. Schulz
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/83703
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact