The paper investigates the seasonal performance of electric air-to-water heat pump comparing an on-off heat pump with an inverter-driven variable speed compressor. Reference is made to a heat pump for domestic space heating installed in Bologna, and the bin-method proposed by UNI/TS 11300-4 is employed in order to investigate the effect of external temperature. The analysis shows that the inverter heat pump performs better than the on-off one, displaying higher values of SCOP about at least 10%.

The scop of an air source heat pump: Comparison between on-off and inverter heat pump

Rossi di Schio E.;Ballerini V.
2021

Abstract

The paper investigates the seasonal performance of electric air-to-water heat pump comparing an on-off heat pump with an inverter-driven variable speed compressor. Reference is made to a heat pump for domestic space heating installed in Bologna, and the bin-method proposed by UNI/TS 11300-4 is employed in order to investigate the effect of external temperature. The analysis shows that the inverter heat pump performs better than the on-off one, displaying higher values of SCOP about at least 10%.
JP JOURNAL OF HEAT AND MASS TRANSFER
Rossi di Schio E.; Ballerini V.