The safety of small and medium LPG (liquefied petroleum gas) storage tanks in civil and industrial facilities when affected by forest fires in the framework of WildlandâUrban Interface (WUI) was investigated. Large scale experimental tests were carried to characterize the behavior of LPG tanks in case of distant source radiation caused by forest fires. A data set was obtained and used for the validation of a dedicated two-dimensional computational fluid dynamic (2D CFD) model for the analysis of pressure build-up in vessels exposed to different types of transient heat radiation, featuring different geometry types and operating conditions. The combined experimental and numerical analysis allowed determining the critical exposure conditions for LPG vessels. Specific key performance indicators were defined and calculated on the basis of 2D CFD simulation results in order to derive conservative indications on failure conditions of LPG storage vessels induced by forest fires.
Scarponi, G.E., Landucci, G., Heymes, F., Cozzani, V. (2018). Experimental and numerical study of the behavior of LPG tanks exposed to wildland fires. PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 114, 251-270 [10.1016/j.psep.2017.12.013].
Experimental and numerical study of the behavior of LPG tanks exposed to wildland fires
Scarponi, Giordano Emrys;Landucci, Gabriele;Cozzani, Valerio
2018
Abstract
The safety of small and medium LPG (liquefied petroleum gas) storage tanks in civil and industrial facilities when affected by forest fires in the framework of WildlandâUrban Interface (WUI) was investigated. Large scale experimental tests were carried to characterize the behavior of LPG tanks in case of distant source radiation caused by forest fires. A data set was obtained and used for the validation of a dedicated two-dimensional computational fluid dynamic (2D CFD) model for the analysis of pressure build-up in vessels exposed to different types of transient heat radiation, featuring different geometry types and operating conditions. The combined experimental and numerical analysis allowed determining the critical exposure conditions for LPG vessels. Specific key performance indicators were defined and calculated on the basis of 2D CFD simulation results in order to derive conservative indications on failure conditions of LPG storage vessels induced by forest fires.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.