The new High Speed railway station of the city of Florence will be located below ground level inside a huge excavation, 25 m b.g.s deep, 450 m long and 50 m wide; the pit, already built, is surrounded by concrete cutoff walls causing a piezometric damming effect against the main aquifer of the Arno River. As permanent mitigation measure against the piezometric mounding, the design of the station considers a series of drain pipes drilled horizontally on up and down gradient sides of the pit and connected by blind wall tubes. A numerical finite differences model has been implemented with the Modflow code, in order to quantify the expected damming effect and to properly design the drain-based mitigation measures (i.e. frequency and length of the drains). One of the major challenges of the numeric approach was the coupling between the groundwater flow in the porous medium and the water flow towards and through the drains and the blind wall tubes connecting the sides of the excavation. Thus, the drains were simulated using a recently published Modflow Process originally developed for karst conduits (Conduit Flow Process - CFP), which allows combining the groundwater flow in the porous medium with laminar or turbulent flow into pipes. In order to guarantee an acceptable head differential between both sides of the excavation, the results showed that the system should permit a discharge flow rate of about 0.026 m3/s, considering a hydraulic gradient equal to 0.5% (i.e. hydraulic gradient from the averaged piezometric distribution before pit excavation). Conductance turned out to be the most influent parameter towards the effectiveness of the drainage system.

Filippini, M., Martina, M.L.V., Stefano, M., Francesco, P., Luca, R., Gargini, A. (2016). Use of the Conduit Flow Process for the simulation of passive mitigation measures against the piezometric damming effect at the new underground High Speed railway station of Florence. RENDICONTI ONLINE DELLA SOCIETÀ GEOLOGICA ITALIANA, 41, 58-60 [10.3301/ROL.2016.92].

Use of the Conduit Flow Process for the simulation of passive mitigation measures against the piezometric damming effect at the new underground High Speed railway station of Florence

FILIPPINI, MARIA;MARTINA, MARIO LLOYD VIRGILIO;GARGINI, ALESSANDRO
2016

Abstract

The new High Speed railway station of the city of Florence will be located below ground level inside a huge excavation, 25 m b.g.s deep, 450 m long and 50 m wide; the pit, already built, is surrounded by concrete cutoff walls causing a piezometric damming effect against the main aquifer of the Arno River. As permanent mitigation measure against the piezometric mounding, the design of the station considers a series of drain pipes drilled horizontally on up and down gradient sides of the pit and connected by blind wall tubes. A numerical finite differences model has been implemented with the Modflow code, in order to quantify the expected damming effect and to properly design the drain-based mitigation measures (i.e. frequency and length of the drains). One of the major challenges of the numeric approach was the coupling between the groundwater flow in the porous medium and the water flow towards and through the drains and the blind wall tubes connecting the sides of the excavation. Thus, the drains were simulated using a recently published Modflow Process originally developed for karst conduits (Conduit Flow Process - CFP), which allows combining the groundwater flow in the porous medium with laminar or turbulent flow into pipes. In order to guarantee an acceptable head differential between both sides of the excavation, the results showed that the system should permit a discharge flow rate of about 0.026 m3/s, considering a hydraulic gradient equal to 0.5% (i.e. hydraulic gradient from the averaged piezometric distribution before pit excavation). Conductance turned out to be the most influent parameter towards the effectiveness of the drainage system.
2016
Filippini, M., Martina, M.L.V., Stefano, M., Francesco, P., Luca, R., Gargini, A. (2016). Use of the Conduit Flow Process for the simulation of passive mitigation measures against the piezometric damming effect at the new underground High Speed railway station of Florence. RENDICONTI ONLINE DELLA SOCIETÀ GEOLOGICA ITALIANA, 41, 58-60 [10.3301/ROL.2016.92].
Filippini, Maria; Martina, MARIO LLOYD VIRGILIO; Stefano, Menichetti; Francesco, Palmiero; Luca, Ranfagni; Gargini, Alessandro
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/579655
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? 0
social impact