Patch antennae suitable for partial discharge detection in power cables have been characterized through laboratory experiments carried out in the time and frequency domain, as well as through PD testing. The results reported in this paper show that helicoidal antennae wrapped around the cable at a distance of few meters from the defect site can provide sensitivities and bandwidth that can allow effective detection of PD in accessories or short cable links
A. Cavallini, G.C. Montanari, A. Salsi (2007). Characterisation of patch antennae for PD detection in power cables. PISCATAWAY : IEEE.
Characterisation of patch antennae for PD detection in power cables
CAVALLINI, ANDREA;MONTANARI, GIAN CARLO;
2007
Abstract
Patch antennae suitable for partial discharge detection in power cables have been characterized through laboratory experiments carried out in the time and frequency domain, as well as through PD testing. The results reported in this paper show that helicoidal antennae wrapped around the cable at a distance of few meters from the defect site can provide sensitivities and bandwidth that can allow effective detection of PD in accessories or short cable linksFile in questo prodotto:
Eventuali allegati, non sono esposti
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.