The causes of changes in dielectric response as a result of thermal and irradiative ageing of cable insulation of ethylene propylene copolymer rubber containing 38 wt.% filler were investigated. Samples were aged in three different combinations of irradiation dose rate and temperature, 0.42 kGy h<sup>-1</sup> at 85°C, and 1.58 kGy h<sup>-1</sup> at 55 and 85°C, and subsequently studied by dielectric spectroscopy, NMR spectroscopy using a portable spectrometer, and tensile testing. The extractable mass fraction and density were determined and related to the imaginary part of the dielectric permittivity at 100 kHz. The ageing led to an increase in the dielectric permittivity, stiffness, density and degree of oxidation, together with a decrease in both strain-at-break and relaxation time, as revealed by NMR spectroscopy. Except for the strain-at-break, the properties changed in a linear fashion with increasing imaginary part of the dielectric permittivity at 100 kHz, with particularly good agreement with respect to the density. As these properties are affected by the degree of oxidation, the results show that both NMR using a portable spectrometer and dielectric spectroscopy can be used as condition monitoring techniques to detect the degree of oxidation in complex systems such as filled copolymers.

Linde, E., Verardi, L., Pourmand, P., Fabiani, D., Gedde, U. (2015). Non-destructive condition monitoring of aged ethylene-propylene copolymer cable insulation samples using dielectric spectroscopy and NMR spectroscopy. POLYMER TESTING, 46, 72-78 [10.1016/j.polymertesting.2015.07.002].

Non-destructive condition monitoring of aged ethylene-propylene copolymer cable insulation samples using dielectric spectroscopy and NMR spectroscopy

FABIANI, DAVIDE;
2015

Abstract

The causes of changes in dielectric response as a result of thermal and irradiative ageing of cable insulation of ethylene propylene copolymer rubber containing 38 wt.% filler were investigated. Samples were aged in three different combinations of irradiation dose rate and temperature, 0.42 kGy h-1 at 85°C, and 1.58 kGy h-1 at 55 and 85°C, and subsequently studied by dielectric spectroscopy, NMR spectroscopy using a portable spectrometer, and tensile testing. The extractable mass fraction and density were determined and related to the imaginary part of the dielectric permittivity at 100 kHz. The ageing led to an increase in the dielectric permittivity, stiffness, density and degree of oxidation, together with a decrease in both strain-at-break and relaxation time, as revealed by NMR spectroscopy. Except for the strain-at-break, the properties changed in a linear fashion with increasing imaginary part of the dielectric permittivity at 100 kHz, with particularly good agreement with respect to the density. As these properties are affected by the degree of oxidation, the results show that both NMR using a portable spectrometer and dielectric spectroscopy can be used as condition monitoring techniques to detect the degree of oxidation in complex systems such as filled copolymers.
2015
Linde, E., Verardi, L., Pourmand, P., Fabiani, D., Gedde, U. (2015). Non-destructive condition monitoring of aged ethylene-propylene copolymer cable insulation samples using dielectric spectroscopy and NMR spectroscopy. POLYMER TESTING, 46, 72-78 [10.1016/j.polymertesting.2015.07.002].
Linde, E; Verardi, L.; Pourmand, P.; Fabiani, D.; Gedde, U.W.
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/554954
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 32
  • ???jsp.display-item.citation.isi??? 25
social impact