This paper reviews results of partial discharge measurements and accelerated life tests performed on models of random and form wound insulation systems subjected to impulse voltage waveforms. The goal is to highlight how the features of the supply voltage affect the partial discharge activity and how this, eventually, reflects on the endurance of the insulation system. The most salient results are that, for both types of insulation systems, short rise times trigger PD of large magnitude, which are able to Erode the insulation system faster than the partial discharges incepted using waveforms with longer rise times. In particular, failure times estimated by tests under sinusoidal voltages can be overly optimistic in assessing the long-term behavior of the insulation system subjected to impulse voltage waveforms. Frequency also is very important, as it controls the interplay between physical and chemical degradation rates. As a result, above partial discharge inception voltage the frequency acceleration rule does not hold, and can lead therefore to excessively optimistic results.

Characteristics of PD under square wave voltages and their influence on motor insulation endurance / Wang, Peng; Cavallini, Andrea; Montanari, Gian Carlo. - In: IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION. - ISSN 1070-9878. - STAMPA. - 22:6(2015), pp. 7367500.3079-7367500.3086. [10.1109/TDEI.2015.005158]

Characteristics of PD under square wave voltages and their influence on motor insulation endurance

CAVALLINI, ANDREA;MONTANARI, GIAN CARLO
2015

Abstract

This paper reviews results of partial discharge measurements and accelerated life tests performed on models of random and form wound insulation systems subjected to impulse voltage waveforms. The goal is to highlight how the features of the supply voltage affect the partial discharge activity and how this, eventually, reflects on the endurance of the insulation system. The most salient results are that, for both types of insulation systems, short rise times trigger PD of large magnitude, which are able to Erode the insulation system faster than the partial discharges incepted using waveforms with longer rise times. In particular, failure times estimated by tests under sinusoidal voltages can be overly optimistic in assessing the long-term behavior of the insulation system subjected to impulse voltage waveforms. Frequency also is very important, as it controls the interplay between physical and chemical degradation rates. As a result, above partial discharge inception voltage the frequency acceleration rule does not hold, and can lead therefore to excessively optimistic results.
2015
Characteristics of PD under square wave voltages and their influence on motor insulation endurance / Wang, Peng; Cavallini, Andrea; Montanari, Gian Carlo. - In: IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION. - ISSN 1070-9878. - STAMPA. - 22:6(2015), pp. 7367500.3079-7367500.3086. [10.1109/TDEI.2015.005158]
Wang, Peng; Cavallini, Andrea; Montanari, Gian Carlo
File in questo prodotto:
File Dimensione Formato  
PP Characteristics_of_PD_under_square.pdf

Open Access dal 01/01/2018

Tipo: Postprint
Licenza: Licenza per accesso libero gratuito
Dimensione 1.13 MB
Formato Adobe PDF
1.13 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/546075
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 54
  • ???jsp.display-item.citation.isi??? 46
social impact