This paper provides some clarification on the subject of the response of multiconductor lines to lightning-originated electromagnetic fields. Specifically, the effect of the presence of more conductors on the line response is analyzed with and without taking into account the ground losses in the surge propagation. The effect of the boundary conditions is also discussed. The presented analysis shows, in particular, that the response of a matched multiconductor lossless line differs from that of a single-conductor line at the same height only in the line currents. The effect of the nearby line conductors on the induced voltages is, indeed, noticeable when the ground losses are taken into account in the surge propagation.

Napolitano, F., Tossani, F., Nucci, C.A., Rachidi, F. (2015). On the transmission-line approach for the evaluation of LEMP coupling to multiconductor lines. IEEE TRANSACTIONS ON POWER DELIVERY, 30(2), 861-869 [10.1109/TPWRD.2014.2318515].

On the transmission-line approach for the evaluation of LEMP coupling to multiconductor lines

NAPOLITANO, FABIO;TOSSANI, FABIO;NUCCI, CARLO ALBERTO;
2015

Abstract

This paper provides some clarification on the subject of the response of multiconductor lines to lightning-originated electromagnetic fields. Specifically, the effect of the presence of more conductors on the line response is analyzed with and without taking into account the ground losses in the surge propagation. The effect of the boundary conditions is also discussed. The presented analysis shows, in particular, that the response of a matched multiconductor lossless line differs from that of a single-conductor line at the same height only in the line currents. The effect of the nearby line conductors on the induced voltages is, indeed, noticeable when the ground losses are taken into account in the surge propagation.
2015
Napolitano, F., Tossani, F., Nucci, C.A., Rachidi, F. (2015). On the transmission-line approach for the evaluation of LEMP coupling to multiconductor lines. IEEE TRANSACTIONS ON POWER DELIVERY, 30(2), 861-869 [10.1109/TPWRD.2014.2318515].
Napolitano, Fabio; Tossani, Fabio; Nucci, Carlo Alberto; Rachidi, Farhad
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/516404
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 32
  • ???jsp.display-item.citation.isi??? 23
social impact