We present a new method for the evaluation of the per unit length (p.u.l.) internal impedances of solid and hollow conductors. Our method is semianalytical, and takes into account the proximity effect arising from currents mutually induced by nearby conductors which, in turn, modify their internal current density distribution and, hence, their impedance. We eventually apply the developed method to the case of a three-core cable and we calculate the voltages induced in its screens by a lightning current.
Alberto Pagnetti, Alain Xemard, Françoise Paladian, Carlo Alberto Nucci (2012). An Improved Method for the Calculation of the Internal Impedances of Solid and Hollow Conductors With the Inclusion of Proximity Effect. IEEE TRANSACTIONS ON POWER DELIVERY, 27(4), 2063-2072 [10.1109/TPWRD.2012.2212466].
An Improved Method for the Calculation of the Internal Impedances of Solid and Hollow Conductors With the Inclusion of Proximity Effect
NUCCI, CARLO ALBERTO
2012
Abstract
We present a new method for the evaluation of the per unit length (p.u.l.) internal impedances of solid and hollow conductors. Our method is semianalytical, and takes into account the proximity effect arising from currents mutually induced by nearby conductors which, in turn, modify their internal current density distribution and, hence, their impedance. We eventually apply the developed method to the case of a three-core cable and we calculate the voltages induced in its screens by a lightning current.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.