This is the second part of an investigation aimed at providing a thorough technical comparison between traditional and alternative overhead power transmission lines based on the loadability characteristics. The previous Part I outlined and applied the fundamentals of the loadability analysis to three comparable single-circuit lines. In Part II, the analysis is broadened to three comparable double-circuit lines: traditional three-phase ac double-circuit lines (assumed as the reference system for the comparison) and bipolar HVDC lines and nonconventional combined ac-dc lines. As in Part I, the loadability analysis takes into account thermal limits, voltage drop, power losses, and - when feasible - steady state and transient stability. Part II also performs an overall comparison among the different systems in single-circuit and double-circuit configuration to draw final conclusions.

The Loadability of Overhead Transmission Lines - Part II: Analysis of Double-Circuits and Overall Comparison / D. Lauria; G. Mazzanti; S. Quaia. - In: IEEE TRANSACTIONS ON POWER DELIVERY. - ISSN 0885-8977. - STAMPA. - 29:2(2014), pp. 518-524. [10.1109/TPWRD.2013.2280963]

The Loadability of Overhead Transmission Lines - Part II: Analysis of Double-Circuits and Overall Comparison

MAZZANTI, GIOVANNI;
2014

Abstract

This is the second part of an investigation aimed at providing a thorough technical comparison between traditional and alternative overhead power transmission lines based on the loadability characteristics. The previous Part I outlined and applied the fundamentals of the loadability analysis to three comparable single-circuit lines. In Part II, the analysis is broadened to three comparable double-circuit lines: traditional three-phase ac double-circuit lines (assumed as the reference system for the comparison) and bipolar HVDC lines and nonconventional combined ac-dc lines. As in Part I, the loadability analysis takes into account thermal limits, voltage drop, power losses, and - when feasible - steady state and transient stability. Part II also performs an overall comparison among the different systems in single-circuit and double-circuit configuration to draw final conclusions.
2014
The Loadability of Overhead Transmission Lines - Part II: Analysis of Double-Circuits and Overall Comparison / D. Lauria; G. Mazzanti; S. Quaia. - In: IEEE TRANSACTIONS ON POWER DELIVERY. - ISSN 0885-8977. - STAMPA. - 29:2(2014), pp. 518-524. [10.1109/TPWRD.2013.2280963]
D. Lauria; G. Mazzanti; S. Quaia
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/275912
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 20
  • ???jsp.display-item.citation.isi??? 16
social impact