In this paper, focus is made on partial discharge (PD) activity in oil-impregnated pressboard used in converter transformers. Voltages over the main insulation of the valve-side windings of the converter transformer were analyzed using the PSIM software. Next, transformer defects were simulated by insulation models to generate PD signals. The dependence of PD inception voltage (PDIV) on the AC plus DC voltages with and without pre-charging is reported along with PD patterns. Experimental results show that: a) using AC plus DC voltages, PDIV values need pre-charging to be estimated accurately, b) activities can be more energetic than those under sinusoidal AC voltages, although repetition rates are generally lower.

Partial discharge activities of pressboard/oil insulation under AC plus DC voltages / Tianyan Jiang;A. Cavallini;G. C. Montanari;Jian Li. - STAMPA. - (2013), pp. 267-270. (Intervento presentato al convegno 2013 IEEE International Conference on Solid Dielectrics (ICSD) tenutosi a Bologna nel July 2014) [10.1109/ICSD.2013.6619797].

Partial discharge activities of pressboard/oil insulation under AC plus DC voltages

CAVALLINI, ANDREA;MONTANARI, GIAN CARLO;
2013

Abstract

In this paper, focus is made on partial discharge (PD) activity in oil-impregnated pressboard used in converter transformers. Voltages over the main insulation of the valve-side windings of the converter transformer were analyzed using the PSIM software. Next, transformer defects were simulated by insulation models to generate PD signals. The dependence of PD inception voltage (PDIV) on the AC plus DC voltages with and without pre-charging is reported along with PD patterns. Experimental results show that: a) using AC plus DC voltages, PDIV values need pre-charging to be estimated accurately, b) activities can be more energetic than those under sinusoidal AC voltages, although repetition rates are generally lower.
2013
2013 IEEE International Conference on Solid Dielectrics (ICSD)
267
270
Partial discharge activities of pressboard/oil insulation under AC plus DC voltages / Tianyan Jiang;A. Cavallini;G. C. Montanari;Jian Li. - STAMPA. - (2013), pp. 267-270. (Intervento presentato al convegno 2013 IEEE International Conference on Solid Dielectrics (ICSD) tenutosi a Bologna nel July 2014) [10.1109/ICSD.2013.6619797].
Tianyan Jiang;A. Cavallini;G. C. Montanari;Jian Li
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/250499
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 8
  • ???jsp.display-item.citation.isi??? 5
social impact