We have investigated recently the role of voltage supply frequency on partial discharge inception voltage (PDIV) measurement for cavities embedded in a polyethylene matrix. From the experimental results, it was ascertained that lower frequencies could lead to lower PDIV values, whereas increasing the supply frequency could quench partial discharge activity. Some explanations were proposed, but a further experimental activity was planned to confirm (or reject) some of the hypotheses. In this paper, the results presented earlier are further validated through an extensive experimental survey. The conclusions derived from the present data are that PDIV does not change appreciably with frequency, whereas, its measured value does. Very low frequency systems seem to provide results that are more accurate than those obtained using higher frequencies

A. Cavallini, V. Krotov, G. C. Montanari, P. H. F. Morshuis, L. E. Mariut (2012). The role of supply frequency in the evaluation of partial discharge inception voltage in XLPE-embedded cavities. Piscataway : IEEE PRESS [10.1109/CEIDP.2012.6378826].

The role of supply frequency in the evaluation of partial discharge inception voltage in XLPE-embedded cavities

CAVALLINI, ANDREA;MONTANARI, GIAN CARLO;
2012

Abstract

We have investigated recently the role of voltage supply frequency on partial discharge inception voltage (PDIV) measurement for cavities embedded in a polyethylene matrix. From the experimental results, it was ascertained that lower frequencies could lead to lower PDIV values, whereas increasing the supply frequency could quench partial discharge activity. Some explanations were proposed, but a further experimental activity was planned to confirm (or reject) some of the hypotheses. In this paper, the results presented earlier are further validated through an extensive experimental survey. The conclusions derived from the present data are that PDIV does not change appreciably with frequency, whereas, its measured value does. Very low frequency systems seem to provide results that are more accurate than those obtained using higher frequencies
2012
2012 Annual Report Conference on Electrical Insulation and Dielectric Phenomena
487
490
A. Cavallini, V. Krotov, G. C. Montanari, P. H. F. Morshuis, L. E. Mariut (2012). The role of supply frequency in the evaluation of partial discharge inception voltage in XLPE-embedded cavities. Piscataway : IEEE PRESS [10.1109/CEIDP.2012.6378826].
A. Cavallini;V. Krotov;G. C. Montanari;P. H. F. Morshuis;L. E. Mariut
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/138001
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 16
  • ???jsp.display-item.citation.isi??? 11
social impact