Recent power quality studies have been focused on the source-identification of voltage disturbances at distribution network busses. This paper describes a method aimed at correlating indirect-lightning events with power systems relay operations, associated with voltage dips. The proposed method, based on the coordinated use of the Italian lightning location system CESI-SIRF, the Italian monitoring system of protection manoeuvres CESI-SAM, and the availability of an advanced simulation tool for the accurate simulation of lightning-induced voltages on complex power networks, namely the LIOV-EMTP code, is applied to the real case of an Italian distribution system. The LIOV-EMTP code is also employed along with a statistical procedure based on the Monte Carlo method to carry out a statistical analysis aimed at assessing the lightning performance of a typical Italian distribution line.
C.A. Nucci, A. Borghetti, M. Paolone, P. Boselli, M. Bernardi, S. Malgarotti, et al. (2004). Lightning-Induced Voltages on Overhead Distribution Lines: Theoretical and Experimental Investigation of related Problems and their Impact on Power Quality. PARIS : CIGRE - Int. Council on Large Electric Systems.
Lightning-Induced Voltages on Overhead Distribution Lines: Theoretical and Experimental Investigation of related Problems and their Impact on Power Quality
NUCCI, CARLO ALBERTO;BORGHETTI, ALBERTO;PAOLONE, MARIO;
2004
Abstract
Recent power quality studies have been focused on the source-identification of voltage disturbances at distribution network busses. This paper describes a method aimed at correlating indirect-lightning events with power systems relay operations, associated with voltage dips. The proposed method, based on the coordinated use of the Italian lightning location system CESI-SIRF, the Italian monitoring system of protection manoeuvres CESI-SAM, and the availability of an advanced simulation tool for the accurate simulation of lightning-induced voltages on complex power networks, namely the LIOV-EMTP code, is applied to the real case of an Italian distribution system. The LIOV-EMTP code is also employed along with a statistical procedure based on the Monte Carlo method to carry out a statistical analysis aimed at assessing the lightning performance of a typical Italian distribution line.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.