The paper presents a frequency-domain method for the analysis of lightning surge response of overhead transmission lines equipped with surge arresters. The model takes into account the frequency dependence of the grounding system. The transmission line is represented in frequency domain by making use of the BLT (Baum- Liu-Tesche) equations while the grounding system, to which the arrester station is connected, is simulated using general electromagnetic model solved by means of the Method of Moment (MoM) in frequency domain. The lightning-originated overvoltages in presence of the surge arrester are then calculated in frequency domain using the Arithmetic Operator Method (AOM). The validity of the proposed approach is tested by comparing its results with those obtained using the Electromagnetic Transient Program (EMTP), for a simple configuration. The efficiency of the proposed technique is demonstrated considering the case of a more complex grounding system.

Impact of Grounding Systems Frequency Dependency on Lightning Arresters Transient Response / K. Sheshyekani; F. Rachidi; S. H. H. Sadeghi; R. Moini; M. Paolone. - ELETTRONICO. - 1:(2009), pp. 1-4. (Intervento presentato al convegno International Conference on Power Systems Transients tenutosi a Kyoto, Japan nel June 2-6, 2009).

Impact of Grounding Systems Frequency Dependency on Lightning Arresters Transient Response

PAOLONE, MARIO
2009

Abstract

The paper presents a frequency-domain method for the analysis of lightning surge response of overhead transmission lines equipped with surge arresters. The model takes into account the frequency dependence of the grounding system. The transmission line is represented in frequency domain by making use of the BLT (Baum- Liu-Tesche) equations while the grounding system, to which the arrester station is connected, is simulated using general electromagnetic model solved by means of the Method of Moment (MoM) in frequency domain. The lightning-originated overvoltages in presence of the surge arrester are then calculated in frequency domain using the Arithmetic Operator Method (AOM). The validity of the proposed approach is tested by comparing its results with those obtained using the Electromagnetic Transient Program (EMTP), for a simple configuration. The efficiency of the proposed technique is demonstrated considering the case of a more complex grounding system.
2009
Proceedings of the 2009 International Conference on Power Systems Transients
1
4
Impact of Grounding Systems Frequency Dependency on Lightning Arresters Transient Response / K. Sheshyekani; F. Rachidi; S. H. H. Sadeghi; R. Moini; M. Paolone. - ELETTRONICO. - 1:(2009), pp. 1-4. (Intervento presentato al convegno International Conference on Power Systems Transients tenutosi a Kyoto, Japan nel June 2-6, 2009).
K. Sheshyekani; F. Rachidi; S. H. H. Sadeghi; R. Moini; M. Paolone
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/83477
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact