Type II insulation systems, typical of MV motors or generators, were aged under sequential thermal cycling and voltage, and diagnostic quantities related to partial discharge activity recorded, such as partial discharge inception voltage (PDIV). Accelerated aging was carried out until breakdown statistics was reached. Sinusoidal and impulsive voltage waveforms were used, with the purpose of comparing breakdown times and PD phenomenology changing supply voltage waveform and rise time. The results undoubtedly indicate that the shape of the waveform, particularly the rise time, can affect dramatically both PD phenomenology and life.

Accelerated aging, partial discharges and breakdown of Type II turn-to-turn insulation system of rotating machines / Montanari, GIAN CARLO; Cavallini, Andrea; Ciani, Fabio; Contin, Alfredo. - ELETTRONICO. - (2016), pp. 7548692.190-7548692.193. (Intervento presentato al convegno 34th Electrical Insulation Conference, EIC 2016 tenutosi a Montreal, Canada nel 2016) [10.1109/EIC.2016.7548692].

Accelerated aging, partial discharges and breakdown of Type II turn-to-turn insulation system of rotating machines

MONTANARI, GIAN CARLO;CAVALLINI, ANDREA;CIANI, FABIO;
2016

Abstract

Type II insulation systems, typical of MV motors or generators, were aged under sequential thermal cycling and voltage, and diagnostic quantities related to partial discharge activity recorded, such as partial discharge inception voltage (PDIV). Accelerated aging was carried out until breakdown statistics was reached. Sinusoidal and impulsive voltage waveforms were used, with the purpose of comparing breakdown times and PD phenomenology changing supply voltage waveform and rise time. The results undoubtedly indicate that the shape of the waveform, particularly the rise time, can affect dramatically both PD phenomenology and life.
2016
34th Electrical Insulation Conference, EIC 2016
190
193
Accelerated aging, partial discharges and breakdown of Type II turn-to-turn insulation system of rotating machines / Montanari, GIAN CARLO; Cavallini, Andrea; Ciani, Fabio; Contin, Alfredo. - ELETTRONICO. - (2016), pp. 7548692.190-7548692.193. (Intervento presentato al convegno 34th Electrical Insulation Conference, EIC 2016 tenutosi a Montreal, Canada nel 2016) [10.1109/EIC.2016.7548692].
Montanari, GIAN CARLO; Cavallini, Andrea; Ciani, Fabio; Contin, Alfredo
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/598774
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 10
  • ???jsp.display-item.citation.isi??? 8
social impact