Hot-water liquid cooling is a key technology in future green supercomputers as it maximizes the cooling efficiency and energy reuse. However the cooling system still is responsible for a significant percentage of modern HPC power consumption. Standard design of liquid-cooling control relies on rules based on worst-case scenarios, or on CFD simulation of portion of the entire system, which cannot account for all the real supercomputer working conditions (workload and ambient temperature). In this work we first introduce an analytical model, based on lumped parameters, which can effectively describe the cooling components and dynamics, and can be used for analysis and control purposes. We then use it to design an energy-optimal control strategy which is capable to minimize the pump and chiller power consumption while, meeting the supercomputer cooling requirements. We validate the method with simulation tests, taking data from a real HPC cooling mechanism, and comparing the results with state-of-the-art commercial cooling system control strategies.

Energy-aware cooling for hot-water cooled supercomputers

CONFICONI, CHRISTIAN;BARTOLINI, ANDREA;TILLI, ANDREA;BENINI, LUCA
2015

Abstract

Hot-water liquid cooling is a key technology in future green supercomputers as it maximizes the cooling efficiency and energy reuse. However the cooling system still is responsible for a significant percentage of modern HPC power consumption. Standard design of liquid-cooling control relies on rules based on worst-case scenarios, or on CFD simulation of portion of the entire system, which cannot account for all the real supercomputer working conditions (workload and ambient temperature). In this work we first introduce an analytical model, based on lumped parameters, which can effectively describe the cooling components and dynamics, and can be used for analysis and control purposes. We then use it to design an energy-optimal control strategy which is capable to minimize the pump and chiller power consumption while, meeting the supercomputer cooling requirements. We validate the method with simulation tests, taking data from a real HPC cooling mechanism, and comparing the results with state-of-the-art commercial cooling system control strategies.
2015
Proceedings -Design, Automation and Test in Europe, DATE
1353
1358
Conficoni, Christian; Bartolini, Andrea; Tilli, Andrea; Tecchiolli, Giampietro; Benini, Luca
File in questo prodotto:
Eventuali allegati, non sono esposti

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11585/541232
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 19
  • ???jsp.display-item.citation.isi??? 14
social impact